Quantitative internal infrared thermography for determining in-situ thermal behaviour of façades

Autor
Tejedor, B.; Casals, M.; Gangolells, M.; Roca, X.
Tipus d'activitat
Article en revista
Revista
Energy and buildings
Data de publicació
2017-09-15
Volum
151
Pàgina inicial
187
Pàgina final
197
DOI
https://doi.org/10.1016/j.enbuild.2017.06.040 Obrir en finestra nova
Repositori
http://hdl.handle.net/2117/106990 Obrir en finestra nova
URL
http://www.sciencedirect.com/science/article/pii/S0378778817301305?via%3Dihub Obrir en finestra nova
Resum
The thermal behaviour of a building is often underestimated or neglected during its construction and operation stages. In recent years, the heat flux meter (HFM) method has been commonly used to determine the U-value, a key parameter for assessing the thermal quality of the building envelope in steady-state conditions. However, this non-invasive test takes at least 72 h to execute, the accuracy is 14–28%, and it is not reliable for non-homogeneous building elements. An alternative technique is...
Citació
Tejedor, B., Casals, M., Gangolells, M., Roca, X. Quantitative internal infrared thermography for determining in-situ thermal behaviour of façades. "Energy and buildings", 15 Setembre 2017, vol. 151, p. 187-197.
Paraules clau
Building façade, Energy performance gap, Quantitative infrared thermography (IRT), Thermal transmittance (U-value) In-situ measurement
Grup de recerca
GRIC - Grup de Recerca i Innovació de la Construcció